In large villas a small heater in every bathroom is not enough. A central system heats water in one place and distributes it to every bathroom and the kitchen. This guide shows how tank size and heating power are calculated.
Daily demand
We start from the number of occupants and an approximate rate of 60 litres per person per day for housing. A villa of six people is about 360 litres a day. This is a starting point, adjusted for the number of bathrooms, bathtubs and family habits.


Heating power
The energy needed comes from the water volume and temperature rise: heating 360 litres from 18 to 60 degrees takes about 17 to 18 kWh. If we want to reheat the tank in two hours, the required power is about 9 kW. The longer the allowed reheat time, the lower the power and the larger the tank.
Tank size
The tank stores hot water to cover the peak hour (the morning, when several bathrooms run). A bigger tank allows a smaller heater. We choose a tank that covers the peak without running out before the water is reheated.
Why a recirculation loop
Without it, water in far pipes cools and you wait minutes for hot water while wasting water. A recirculation loop keeps hot water moving with a small pump so it arrives instantly. Pipes must be well insulated to limit heat loss, and return temperature should stay around 50 degrees or more.


What is installed
- One or more storage tanks.
- A heater, boiler or heat pump.
- A recirculation pump and insulated pipes.
- Safety valves and an expansion vessel.
Frequently asked questions
Heater per bathroom or a central system?
For large villas central is better. In small apartments separate heaters may be enough.
Do I always need a recirculation loop?
If distances are long or you want instant hot water, yes.
Can hot water be tied to the heating boiler?
Yes, and the boiler is sized for both loads.